Product: | ISaGRAF 4.03 |
Date: | 25-September-2000 |
File: | Configuration Manager Serial Link Start option.htm |
Subject: | How to start configuration manager so that it uses serial link |
Keywords: | Configuration manager - ISaRSI - CMG - ETCP - ISaGRAF |
____________________________________________________________________
Arguments can be passed when starting Configuration manager (CMG):
ETCP task will not be started
Example1 working on Windows NT : ISaGRAF -RSI=COM1:19200:N:1:OFF -NoETCP.
Example 2 working on Windows NT: create a ‘isagraf.ini’ file that contains lines below, and start CMG with no parameter on command line.
[APP]
NoETCP=1
ResNbr=20
s=1
RSI=COM1:19200:N:1:OFF
____________________________________________________________________
Copyright © 1999-2009 ICS Triplex ISaGRAF Inc. All rights reserved.